DriversRecommendedOutdated drivers can make a good PC feel brokenScan driver issues before chasing fixes manually.Scan NowHalloween DealsAmazon USHalloween week deals: useful picks before month-endAmazon US: current deals, useful picks and tech finds.Check DealsClean PCRecommendedOne scan can reveal what keeps slowing WindowsLook for cleanup and repair opportunities.Run Scan×
FREEDOM251

Freedom251 › Blog › cooling towers

How to Measure and Reduce Water Use in a Data Center

By Freedom251 Team · · 10 min read

Free tools Windows power users keep installed

One-click scans. No signup required.

Special offer. See more information about Outbyte and uninstall instructions. Please review EULA and Privacy policy.

The reliable way to manage data-center water is to establish a clearly defined facility boundary, measure every relevant water input, measure IT energy over the same period, and calculate Water Usage Effectiveness (WUE) in liters per kilowatt-hour. Then reduce avoidable use by tuning controls, improving cooling-tower operation and checking whether alternative cooling methods fit the site’s climate, water chemistry, reliability needs and energy objectives.

WUE is an intensity metric, not a complete water-impact statement. Publish the ratio together with annual water volume, water source and quality, reporting period, facility scope and local context.

As an Amazon Associate I earn from qualifying purchases.

What WUE measures—and what it does not

The U.S. Department of Energy Federal Energy Management Program (DOE FEMP) gives the practical calculation:

Special offer. See more information about Outbyte and uninstall instructions. Please review EULA and Privacy policy.

WUE = annual site water usage (liters) ÷ annual IT equipment energy use (kWh)

#1 Best Overall
Sale
Nicpro Mechanical Carpenter Pencils for Construction (Black, Red) With Case | Deep Hole Marker Pencil Set Includes Sharpener and 26 Refills, Comfortable Grip, Heavy Duty Woodworking Tools for Architect
  • Valued Carpenter Pencil Set: You will get 2 pcs solid carpenter pencils with 26 piece 2.8 mm refills, 1 replaceable sharpener, 1 plastic storage box.The complete carpenter pencils combination allows you to finish your work faster and more easily
  • Deep Hole Marker Pencil: The deep-hole construction pencils adopts 45mm elongated tip design, which is more convenient to mark in the small hole or in other tight areas that other carpenter markers cannot reach
  • Carpenter Pencils with Sharpener: The sharpener is screwed into the top of the work pencil, which won't get lost either. Built-in pencil sharpener that keep the lead with pointed and smooth to Improves line of sight in fine work
  • Stronger Solid Lead: This work pencil is matched with a 2.8 mm thick lead , which is much thicker and stronger during the drawing process of construction work, it will not break or damage easily
  • Marks on Various Surfaces: 3 colors solid construction pencil can marks on various surfaces,such as metal, plastic, wood, paper etc. Ideals for woodworkers, contractors, craftsmen, builders, merchants and masons

The result is expressed in liters per kilowatt-hour (L/kWh). The numerator is water used by the defined data-center site during the reporting year; the denominator is energy consumed by IT equipment during that same period and under the selected measurement method.

ISO/IEC 30134-9:2022 specifies WUE as a data-center key performance indicator for the use phase, including categories, measurement, calculation, reporting and interpretation. Use the standard’s exact category definitions when you need a formal comparison or compliance-grade report.

A lower ratio means less measured water per unit of IT energy within the stated boundary. It does not, by itself, prove lower total environmental impact. A cooling change can reduce direct water use while increasing electricity demand and associated emissions. Conversely, water cooling can reduce energy consumption and related carbon emissions compared with air-based systems in some configurations. Location, humidity, ambient temperature, water source and local availability all affect the result.

Special offer. See more information about Outbyte and uninstall instructions. Please review EULA and Privacy policy.

Keep these terms separate in your ledger:

  • Water withdrawn or supplied: water entering the facility boundary from a utility, well or other source.
  • Water consumed: the portion not returned to the source in the same form or location, according to the accounting definition you adopt.
  • Water discharged or returned: water leaving the boundary, such as cooling-tower blowdown or treated effluent.

Do not substitute one term for another. State which quantity appears in your WUE numerator and how return flows are treated.

Set a defensible data-center boundary first

WUE comparisons fail when sites count different equipment or shared building services. Write the boundary before installing meters or downloading utility data.

Define included spaces and systems

Document the buildings, rooms and plant systems that serve the data center. Decide whether the boundary includes:

  • IT rooms and the energy used by servers, storage and networking equipment;
  • chillers, pumps, cooling towers, dry coolers, heat exchangers and associated treatment systems;
  • humidification equipment;
  • maintenance, testing and other water uses that support data-center operation; and
  • shared building services such as toilets, kitchens or general HVAC.

For a mixed-use building, either install separate meters or transparently estimate the data-center share. Record the allocation method and keep it consistent from year to year. A change from measured allocation to an unsupported estimate can create an apparent WUE improvement that is only an accounting change.

Special offer. See more information about Outbyte and uninstall instructions. Please review EULA and Privacy policy.
Rank #2
Sale
DEWALT 20V MAX Drill and Impact Driver (DCK240C2) | Includes 2 Batteries, Charger and Bag (
  • Ergonomically Designed: Work in tight areas with a compact design that gets into tough spots
  • Both tools are designed to fit into difficult to reach spaces
  • Complete a wide range of applications with a high-performance motor that delivers up to 300 UWO, and an impact driver delivering up to 1,400 in-lbs of torque
  • Both the DEWALT impact driver and drill driver feature integrated LED work lights with a convenient 20-second delay, ensuring enhanced visibility in dimly lit or challenging work areas
  • One-Handed Loading - Keep one hand free with a 1/4 in. hex chuck that accepts 1 in. bit tips

Match the boundary to reporting rules

EU Commission Delegated Regulation (EU) 2024/1364 requires reporting centers to measure water volumes entering the boundary and used for data-center functions and to identify the WUE category. It references EN 50600-4-9 methodology or an equivalent. This is a jurisdiction-specific requirement, not a rule for every facility worldwide. Check the current regulation and the rules that apply to your location before making a compliance claim.

When comparing two sites, require the same boundary, WUE category, reporting period and treatment of shared uses. If they differ, present the figures as separate disclosures rather than as a ranking.

How do I measure water use in a data center?

Use a documented water balance. The following sequence creates an auditable baseline.

  1. Freeze the scope and period. Name the facilities, systems and services in the boundary. Choose a full 12-month period, normally a fiscal or calendar year, and record the start and end dates.
  2. List every source and use. Identify potable, reclaimed, rainwater, well or other supplies. Map where each source goes: cooling-tower makeup, humidification, process systems, sanitation and other facility uses. Record water quality because treatment requirements and allowable cycles depend on chemistry.
  3. Reconcile bills with site meters. Collect utility invoices and main-meter readings for the same dates. Investigate differences caused by billing estimates, meter resets, leaks, reading dates or water that serves non-data-center tenants.
  4. Add submeters at major branches. A total facility meter establishes the input. Submeters can isolate cooling-tower makeup, humidification and other large users. DOE metering resources specifically discuss submetering water, and its metering best-practices guide describes cooling-tower makeup metering as a way to identify abnormal flow.
  5. Verify meter suitability and data quality. Select and install instruments according to pipe size, flow range, water quality, pressure, installation conditions and the site’s instrumentation requirements. Keep calibration, maintenance and data-logging records. There is no single meter type or model that fits every facility.
  6. Measure IT energy over the identical period. Apply the boundary and method required by your chosen standard or reporting rule. Retain the underlying interval or billing records instead of keeping only the final annual total.
  7. Calculate and review WUE. Divide annual site water usage in liters by annual IT equipment energy in kilowatt-hours. Have operations and finance or sustainability staff review the inputs before publication.
  8. Publish the context. State the boundary, category, dates, sources, water quantity definition, allocation method, data quality and any estimated values. Report absolute annual water volume alongside WUE.

Build a water ledger

A simple ledger makes unexplained changes visible. Keep at least these fields for each source and use:

Special offer. See more information about Outbyte and uninstall instructions. Please review EULA and Privacy policy.
Ledger field What to record
Source Utility, well, reclaimed or other supply
Point of measurement Main meter or named submeter and its physical location
Water quality Potable, reclaimed or other specified quality
Use Cooling-tower makeup, blowdown, humidification, sanitation or another defined use
Period Reading dates and the annual reporting interval
Quantity and unit Metered volume with the original unit and converted liters
Data status Actual reading, utility bill, allocation or documented estimate

Reconcile the sum of branch meters to the facility input. A persistent gap may indicate an unmetered branch, leak, meter error or a boundary assumption that was never documented.

Calculate and communicate WUE without misleading comparisons

Use one numerator and one denominator

Convert all water readings to liters and all IT energy records to kilowatt-hours before division. Use the same dates for both. If a site opened partway through the year, state the partial period rather than annualizing it without explanation.

For an illustrative calculation, a site that records 8,760,000 liters of in-boundary water and 12,000,000 kWh of IT energy for the same year would report 0.73 L/kWh. This is an arithmetic example, not a performance benchmark.

Rank #3
Sale
Push to Unlock,Katerk 6pcs 1/4 inch Hex Shank Aluminum Alloy Screwdriver Bit Holder Light-Weight Quick-Change Extension Bar Keychain Drill Screw Adapter Portable,Black Carabiner,Tool Gifts for Men
  • 【Great Compatibility】This Katerk 1/4 inch hex shank bit holder is specifically designed for 1/4 inch hex shank drill bits. It's compatible with most 1/4 fast hex handles, hex sockets, various electric screwdrivers, and handheld screwdrivers. The bit holder makes it a valuable addition for any handyman.
  • 【Secure and Safe】Built with a secure backup nut design, each drill bit holder securely locks onto your bits, ensuring they stay firmly in place. Additionally, our bit holder incorporates a high-quality steel ball rolling design that holds up to several kilograms of weight, ensuring your various drill bits don't fall off.
  • 【Easy One-Handed Operation】The bit holder for impact driver allows you to change bits single-handedly, simplifying your workflow. Its multi-color design further allows for quick identification of the drill bit you need.
  • 【Compact and Convenient】Thanks to its compact size, this 1/4 inch bit holder is easy to carry around. The bit holder allows for easy attachment to various tools, making this a convenient addition to your construction accessories. The Katerk bit holder is cast from high-quality alloy material, promising a long product lifespan. Despite its rugged strength, the bit holder remains lightweight, making it portable.
  • 【Cool Christmas Gift For Men Stocking Stuffers】 This screwdriver bit holder, driver bit holder, impact bit holder, can be given as a gift to your loved one, especially for anyone involved in construction or electrical work. It's a must-have for stocking stuffers for men and women, tools gifts for dad, tech gadgets for men, gifts for dad, gifts for him, gifts for husband, gifts for boyfriend, cool gadgets for men, and cool gifts for dad.

Report the ratio with absolute water

WUE can improve because IT energy rises faster than water use, even while total water demand increases. Conversely, a smaller facility can have a low annual volume but a high intensity. Publish both figures, along with source and quality, so readers can see the actual demand and the efficiency ratio.

Special offer. See more information about Outbyte and uninstall instructions. Please review EULA and Privacy policy.

Use operator figures as disclosures, not targets

Microsoft reports a global FY25 WUE of 0.27 L/kWh for July 1, 2024 through June 30, 2025. Its stated scope is datacenters it fully owns and controls that had been operational for 12 months at the time of calculation. The same page reports the following regional values:

Microsoft FY25 region Reported WUE Scope and period
Global 0.27 L/kWh Datacenters fully owned and controlled, operational for 12 months; July 1, 2024–June 30, 2025
Americas 0.34 L/kWh Microsoft’s stated facility scope and FY25 period
Asia Pacific 0.25 L/kWh Microsoft’s stated facility scope and FY25 period
Europe, Middle East and Africa 0.03 L/kWh Microsoft’s stated facility scope and FY25 period

These regional differences are not a controlled comparison of cooling systems: climate, humidity, facility age, design and operating conditions vary. No industry-wide “good WUE” threshold is established by the cited DOE and ISO material. A benchmark is meaningful only when boundaries, categories, periods, climate and cooling designs are comparable.

Where data-center water is normally used

Cooling-tower evaporation

Evaporation removes heat from the circulating water in an evaporative tower. It is a direct water demand that rises with rejected heat and operating conditions.

Cooling-tower blowdown

As water evaporates, dissolved minerals remain in the circulating loop. Operators discharge a portion as blowdown to control concentration and add makeup water. Both streams belong in the water balance.

What’s actually slowing this PC down?

Pick the symptom - the matching free tool is one click away.

Special offer. See more information about Outbyte and uninstall instructions. Please review EULA and Privacy policy.

Humidification and other facility uses

Humidification can be significant in climates or operating regimes that require it. Include it, along with sanitation, maintenance and any process use that falls inside the boundary. Do not assume the cooling tower is the only material consumer.

How can a data center reduce water use?

Tune temperature and humidity controls

DOE FEMP notes that data-center temperatures are often held below recommended setpoints and that humidity may be controlled more narrowly than necessary. Review actual setpoints against applicable equipment and thermal guidance. Where the IT equipment, controls and facility design permit, widen operating ranges gradually and monitor reliability, alarms, hardware health and environmental excursions.

Rank #4
2 Pack Carpenter Pencils Mechanical Pencils with 12 Refills, (2 Colors) | Construction Pencils with Built-in Sharpener, Long Nib Deep Hole Pencil Marker, Heavy Duty Woodworking Pencil for Architect
  • Long Nib and Deep Hole Marker: Our mechanical carpenter pencil with 45mm nib is designed for easy marking of deep holes or narrow areas. These construction pencils are the great choice for woodworking tools, construction tools, carpenter tools, contractor tools, wood carpentry tools and architect tools
  • Extra Refills in 2 Colors for Versatile Marking: The construction mechanical pencil comes with 12 extra 2.8mm refills, including 6 red and 6 black refills. The black refill is suitable for light surfaces, while the red wax is perfect for dark surfaces. Our carpenter mechanical pencil makes sure that you'll have an ample supply for extended use
  • Built-in Sharpener: Our construction pencil comes with a built-in sharpener to ensure the mechanical pencil tip is always sharp and ready for use. Never buy an extra pencil sharpener again. A great tool for any woodworker pencil, contractor pencils. The refill can easily be extended or retracted with a simple click of the pencils mechanical, allowing you to work more efficiently and accurately
  • Portable Clip Design: Our deep hole construction pencil features a portable clip design, easy to carry and attach to your pocket or tool box, so that you can keep the carpenter pencils mechanical close at hand, making it a convenient tool to have on the go. Great gifts choice for carpenters
  • Stronger Pencil Lead: The black refills are made of lead, sturdy and smooth. The red refills are made of wax, clear and light. These marking pencils are much thicker and stronger than normal pencils during the marking process of construction work, suitable for various surfaces, such as glasses, metal, boards, floors, walls, furniture, etc. The written marks can be easily wiped with a wet paper towel when needed

Reducing unnecessary cooling load can reduce the heat that must be rejected, but verify both water and energy results. A control change that saves tower water while increasing chiller electricity may not improve the site’s total impact.

Optimize cooling-tower cycles of concentration

Cycles of concentration describe the dissolved-mineral concentration in circulating water relative to makeup water. Increasing cycles can reduce blowdown and makeup demand, but the safe limit depends on water chemistry, treatment, corrosion, scaling, biological control and equipment constraints.

Special offer. See more information about Outbyte and uninstall instructions. Please review EULA and Privacy policy.

DOE FEMP, citing its Cooling Tower Best Management Practice, reports that increasing cycles from three to six reduces cooling-tower makeup-water requirements by 20% and cooling-tower blowdown by 50%. Treat these as guidance figures for that specified operational change, not a guaranteed result at every site. Have qualified facilities and water-treatment staff establish and validate the operating limit.

Use water-side economizing where the plant supports it

Water-side economizing uses an integrated heat exchanger so the cooling tower can cool the chilled-water loop during mild outdoor conditions, bypassing or reducing chiller work. In suitable designs and climates it can reduce water and energy use, but the result depends on the plant configuration, ambient conditions and control sequence.

DOE notes that compressor heat can contribute up to 20% of the cooling-tower system’s total heat-rejection requirement in the described configuration. That figure is context from the guidance, not a guaranteed saving for another facility.

Find and correct abnormal flow

Trend the main meter and cooling-tower makeup submeter against IT load, outdoor conditions, tower operating hours and treatment activity. A sudden increase without a corresponding load or weather change warrants an inspection for leaks, stuck valves, failed controls, overflow, meter faults or an unrecorded use. Keep the investigation record with the annual water ledger.

Special offer. See more information about Outbyte and uninstall instructions. Please review EULA and Privacy policy.

Match water quality to the design

Reclaimed water may reduce potable-water demand where it is available and approved for the intended use. Its mineral and biological characteristics can change treatment requirements and allowable cycles. Evaluate source reliability, seasonal availability, treatment cost, discharge limits and equipment warranties before switching sources.

Best Value
Milwaukee 48-22-3104 Inkzall Point Marker, Fine, Black, 4-Pack
  • Milwaukee Ink all Fine Point Marker, Black, 4 Per Pack
  • 4 per pack Features Clog Resistant Marker Tip Writes through Dusty, Wet and Oily Surfaces Durable Marker Tip for Writing on Concrete, OSB and Rough Surfaces
  • Clog resistant tip writes on dusty, wet and oily surfaces and is optimized for rough surfaces such as OSB, cinderblock and concrete
  • Hard hat clip- attaches for easy access
  • Quick dry time with reduced smearing and marking

DOE FEMP describes “a variety of low-cost, no-cost, operations and maintenance (O&M) related water-saving opportunities” as options for existing federal data centers. The practical implication is to begin with setpoints, controls, leaks, meter visibility and tower operation before committing to a major plant retrofit.

Independent reader supportYour contribution helps us test, update, and keep practical guides available for everyone.Support on Ko-Fi

Compare cooling choices with a water-and-energy lens

Do not label air cooling, liquid cooling or evaporative cooling as universally best. Compare the complete operating context:

Decision axis Questions to answer
Direct water How much water enters the boundary, how much is consumed or discharged, and which sources and qualities are used?
Energy and emissions Will the option increase or reduce chiller, fan, pump or treatment energy, and what emissions follow from the local electricity supply?
Local water context Is water available year-round? What are watershed conditions, drought exposure and seasonal restrictions?
Reliability How does performance change with local temperature, humidity and extreme weather?
Measurement quality Can the option be isolated with meters and reported under a consistent WUE boundary and category?
Retrofit and operations What structural changes, treatment, controls, maintenance and operating limits are required?

Google describes campus decisions as balancing carbon-free energy with responsibly sourced water and says water cooling can reduce energy consumption and related carbon emissions compared with air-based cooling. Microsoft likewise notes that location, humidity and ambient temperatures affect WUE. These statements support a site-specific assessment, not a universal technology ranking.

Special offer. See more information about Outbyte and uninstall instructions. Please review EULA and Privacy policy.

A practical implementation plan

Phase 1: establish the baseline

  • Approve the written boundary and WUE category.
  • Collect 12 months of utility bills, main-meter readings and IT-energy records.
  • Map every source, use, discharge and shared service.
  • Flag estimates, missing months and allocation assumptions.

Phase 2: improve visibility

  • Install or verify submeters on cooling-tower makeup and other major branches.
  • Set a data-retention process for readings, calibration and maintenance.
  • Reconcile branch totals to the main meter each reporting period.

Phase 3: operate for lower demand

  • Review temperature and humidity setpoints against equipment guidance.
  • Test tower cycles with water-chemistry and treatment staff.
  • Check whether water-side economizing is available in the existing plant.
  • Investigate unexplained flow and correct leaks or control faults.

Phase 4: publish and review

  • Calculate WUE from the matched annual water and IT-energy records.
  • Publish absolute water volume, source, quality, boundary, category, dates and data limitations.
  • Compare only with sites using comparable definitions.
  • Revisit the baseline after any major cooling, occupancy or boundary change.

Troubleshoot common WUE reporting problems

WUE suddenly increases

Check for a leak, tower overflow, failed valve, abnormal blowdown, humidifier fault, meter reset or missing IT-energy data. Confirm that the reporting period and unit conversions did not change.

WUE improves but water volume rises

Look at the two absolute totals. The denominator may have grown faster than the numerator. Report both numbers rather than presenting the lower ratio as an unconditional reduction.

Two facilities show very different ratios

Compare boundary, WUE category, climate, humidity, cooling design, water source, operating period and data quality before drawing a conclusion. A regional value is not evidence that one cooling system is inherently superior.

The main meter and submeters do not reconcile

Check reading dates, unit conversions, meter calibration, unmetered branches, shared tenants, leaks and discharge paths. Document the unresolved difference and identify whether the annual numerator is measured or estimated.

Special offer. See more information about Outbyte and uninstall instructions. Please review EULA and Privacy policy.

What a credible annual disclosure contains

A concise but defensible report should state:

  • the facilities and systems inside the boundary;
  • the WUE category and calculation method;
  • the reporting dates;
  • annual site water usage in liters and the definition used;
  • annual IT equipment energy in kilowatt-hours;
  • the resulting WUE in liters per kilowatt-hour;
  • water sources and qualities;
  • shared-use allocation methods;
  • metering coverage, estimates and known data gaps; and
  • local water, climate and operating context where it affects interpretation.

This format lets a reader distinguish a real operational change from a change in scope or accounting.

Product prices and availability are accurate as of the date/time indicated and are subject to change. Any price and availability information displayed on Amazon at the time of purchase will apply.

cooling towersdata center sustainabilitydata centersfacility operationswater usage effectivenessWUE

Leave a Reply

Your email address will not be published. Required fields are marked *

Special offer. See more information about Outbyte and uninstall instructions. Please review EULA and Privacy policy.

Recommended PC Tool
Recommended PC Tool
Outdated Drivers Are Slowing You DownFree scan - exact matches
PC Slower Than It Used to Be?Free scan - under a minute

Two free Windows tools

One Free Minute Could Fix That PC

Before you go - each of these free tools takes about a minute and tackles what quietly slows a Windows PC down.

Special offer. View Outbyte info, uninstall instructions, EULA, and Privacy Policy.