Halloween DealsAmazon USHalloween week deals: useful picks before month-endAmazon US: current deals, useful picks and tech finds.Check DealsWindows FixRecommendedWindows errors stealing your time? Find the fix fastScan stability, cleanup and performance issues.Fix NowHalloween DealsAmazon USOctober picks are moving - compare before checkoutAmazon US: current deals, useful picks and tech finds.See Picks×
FREEDOM251

Freedom251 › Blog › Electricity Costs

How to Calculate Emissions and Electricity-Cost Savings When a Factory Switches to Renewable Power

By Freedom251 Team · · 13 min read

Special offer. See more information about Outbyte and uninstall instructions. Please review EULA and Privacy policy.

Calculate the result in two separate ledgers: one for electricity-related emissions and one for money. First compare the same factory load, months and operating conditions before and after the switch. Then multiply metered kilowatt-hours by an emissions factor that matches the factory’s geography and accounting claim. For costs, compare every bill component—not just the energy rate—including demand, connection, balancing, storage and maintenance charges.

There is no universal grid factor that is safe for every factory. A defensible calculation identifies whether it is location-based, market-based, project-displacement or lifecycle accounting, records the factor’s year and geography, and shows a low/base/high range for uncertain inputs.

As an Amazon Associate I earn from qualifying purchases.

The calculation at a glance

Use this sequence for a renewable-power project, whether it is an onsite solar installation, a renewable power-purchase agreement (PPA), a green tariff or a combination of these options.

Special offer. See more information about Outbyte and uninstall instructions. Please review EULA and Privacy policy.
  1. Set the boundary and comparison period. Use the same months, production volume and operating conditions for the baseline and renewable case.
  2. Measure electricity. Export interval-meter data or install submeters. Reconcile active-energy kWh to utility bills.
  3. Select the factor basis. Choose a current location-based factor, supplier-specific contractual factor, approved project-displacement factor or lifecycle factor, depending on the claim being made.
  4. Calculate baseline emissions. Baseline emissions (tCO2e) = baseline electricity (kWh) × baseline factor (kgCO2e/kWh) ÷ 1,000.
  5. Calculate renewable-case emissions. Apply the residual-grid or supplier factor to electricity still purchased from the grid, then add any renewable-instrument or lifecycle emissions required by the chosen standard.
  6. Calculate avoided emissions. Emissions savings (tCO2e) = baseline emissions − renewable-case emissions.
  7. Calculate bill savings. Subtract the renewable case’s complete electricity cost from the baseline’s complete cost.
  8. Test uncertainty and preserve evidence. Run low, base and high cases and retain meters, bills, contracts, certificates, factor workbooks, formulas and approvals.

The electricity and financial ledgers should be connected by the same interval data, but they should not be merged into one claim. A lower bill does not automatically prove a physical emissions reduction, and a renewable certificate claim does not automatically represent hourly displacement at the factory.

#1 Best Overall
SUNGOLDPOWER UL61730 10PCS 550W Solar Panels Monocrystalline,Waterproof IP68,High Efficiency Solar Panel for Charging Station,Household,Marine,On/Off Grid Solar System (Total 5500W)
  • 【Grade A solar cells】 : The long-lasting UL61730 550W monocrystalline grade A solar cells, the waterproof design ensures that the panel can be used in all weather conditions.
  • 【High Tolerance】: SUNGOLDPOWER UL61730 550W Solar panels are designed for industrial and professional applications using scratch resistant anodized aluminum with a twin wall frame. The tough, sealed, aluminum frame will give you years and years of consistent, free power.
  • 【Widely Use】: Easy Installation with pre-drilled hole. Corrosion-resistant aluminum frame for extended outdoor use. Suitable for Caravan, RV, Golf car, Electric car, Yacht, Boat, Tent or backpack etc.
  • 【High Efficiency】: High modules conversion efficiency. Grade A solar cell and IP68 Rated waterproof solar panel connectors. This solar panel has 5 year 95% output warranty, 10 year 90% output warranty, 25 year 80% output warranty.

Define the factory boundary and baseline

Write the boundary before collecting numbers. For electricity accounting, the project electricity system is the physically connected, dispatchable network serving the site. UNFCCC Tool 7 describes that system as plants connected through transmission and distribution lines and dispatchable without significant transmission constraints.

Choose a comparison period

Use a complete period that represents normal operations—usually 12 consecutive months when data are available. The baseline and renewable case must cover the same months or be normalized for known changes. Record production volume, shifts, weather-sensitive loads, planned shutdowns, new equipment and unusual outages. If production rises after the switch, separate that load growth from the effect of renewable procurement.

Describe the counterfactual

The counterfactual is what would probably have happened without the project. In the ordinary case, it is continued procurement from the same grid and tariff under the observed load, adjusted for documented production changes. The UK ICF KPI 6 methodology expresses avoided emissions as conventional generation avoided × emission factor and requires an estimate of the counterfactual.

Special offer. See more information about Outbyte and uninstall instructions. Please review EULA and Privacy policy.

If the counterfactual cannot be estimated reliably, the UK methodology allows an adjustment factor proportional to confidence and data quality. Document the assumption rather than presenting the full theoretical reduction as certain.

Measure electricity at the right resolution

Obtain interval-meter exports in 15-minute, 30-minute or hourly intervals where possible. Interval data reveal demand peaks, time-of-use prices, curtailment and the hours in which onsite generation is actually serving the factory. Monthly bills alone can support a rough annual calculation, but they cannot reliably allocate demand charges or demonstrate hourly matching.

Reconcile meter data to bills

  1. Export active-energy readings for every interval in the comparison period.
  2. Check that the meter’s register, time zone, daylight-saving treatment and multiplier are documented.
  3. Sum the intervals by billing period and compare the result with the utility bill’s billed kWh.
  4. Investigate gaps, estimated reads, negative values, duplicated intervals and unexplained differences before calculating emissions.
  5. Keep the original export and a controlled, corrected copy so a reviewer can reproduce the transformation.

EU Regulation 2025/2547 specifies that the activity level for embedded-emissions purposes refers to net electricity leaving the system boundaries of a power plant or cogeneration unit. It also specifies that real power, not apparent power, is metered and that reactive power is disregarded. Apply that principle consistently: use real, active energy in kWh and state whether the data represent imported electricity, onsite generation, exports or net consumption.

When the site lacks usable interval data

A three-phase electricity meter or power logger can provide the missing physical record. The voltage class, current-transformer arrangement, communications method and installation location must match the site, and a qualified electrician should select and install the equipment. A logger that is incorrectly rated or placed on the wrong side of a transformer can produce a precise-looking but unusable result.

Special offer. See more information about Outbyte and uninstall instructions. Please review EULA and Privacy policy.

Select an emissions-factor basis

Factor selection determines what the emissions number means. Put the basis, geography, reporting year, unit and source in the calculation file.

Accounting basis What it represents Data to retain Appropriate use
Location-based Average emissions intensity of the grid region where the factory consumes electricity. Country, balancing area or utility region; factor year; unit; workbook or publication. Physical grid-consumption reporting when no qualifying contractual instrument is being claimed.
Market-based The contractual product procured by the customer, such as a qualifying supplier product or PPA, after applying the applicable residual mix or supplier factor to remaining grid electricity. Contract, energy-attribute certificates, delivery period, matching rules and supplier-specific factor. Reporting a contractual procurement choice under a standard that permits it.
Project-displacement Estimated generation and emissions displaced by a project, rather than the average electricity physically consumed. Approved methodology, operating margin, build margin, combined margin, dispatch assumptions and counterfactual. Project claims that explicitly quantify displacement.
Lifecycle Emissions across the renewable technology’s lifecycle, not only operating emissions. Technology, lifecycle boundary, study source, version and included stages. Comparisons that require construction, fuel, maintenance or end-of-life emissions.

These bases are different claims. Do not combine a location-based grid factor, a market-based certificate claim and a project-displacement factor into one unlabeled figure.

Location-based factors

For physical grid consumption, use a current factor for the relevant country, balancing area or utility region. The factor must match the reporting year and the geography in which the factory is connected. A national average may be inappropriate when the site reports against a balancing-area or utility-specific requirement.

Supplier and PPA factors

For a qualifying supplier product or PPA, use the supplier-specific contractual factor and retain the energy-attribute evidence. State the delivery period, whether certificates are bundled or unbundled, and how electricity that remains on the grid is treated. A contractual renewable claim should not be described as a physical, hourly reduction unless the evidence and accounting method support that statement.

Special offer. See more information about Outbyte and uninstall instructions. Please review EULA and Privacy policy.

Project-displacement factors

UNFCCC Tool 7 distinguishes the operating margin, build margin and combined margin. The operating margin reflects existing generation affected by a change in dispatch. Its simple option is a generation-weighted average of CO2 emissions per unit of net generation from serving plants, excluding low-cost or must-run units. The build margin represents prospective generation affected by the project. The combined margin is a weighted average of operating and build margins.

Verra’s VT0011 procedure has been active since 6 February 2025 for estimating electricity-system emission factors where the applicable methodology requires it. Use the procedure only within the methodology and project scope for which it is applicable.

Maintain current factor files

The US Environmental Protection Agency’s Emission Factors Hub is regularly updated and draws on EPA programs, eGRID, the US inventory and IPCC AR5. Its 2025 update added purchased-electricity factors and grid gross-loss percentages for eGRID subregions. For UK reporting, the government’s company-reporting factors are an annual series; the collection records the 2026 conversion factors as added on 11 June 2026. Save the exact workbook, factor name, geography, unit and publication year with the calculation.

Rank #2
ECO WORTHY 10000W Output Complete Off-Grid Solar Panel Kit for Home| 10KW 120V/240V Output Split Phase Inverter| 48V 314Ah16.1kWh High Capacity Energy Storage| 2950W Solar Panel PV| Whole House System
  • System Components:Delivers up to 10kW power output with 120V/240V single-phase split-phase support, making it suitable for smoothly running common household appliances. The system includes 5 × 590W solar panels with a total PV capacity of 2950W, capable of generating up to 11.8 kWh per day under optimal conditions, along with one 48V 314Ah portable LiFePO₄ battery offering 16.1 kWh of energy storage. Complete with necessary cables, this all-in-one solar solution is designed for convenient setup and reliable home power support.
  • Upgraded Integrated Battery:ECO-WORTHY 48V 314Ah lithium battery combines advanced safety, high capacity, and smart system compatibility. It features a PACE 200A Battery Management System with multi-layer protection and dual breakers for reliable circuit safety. With a 16.076 kWh energy capacity and support for up to 15 units in parallel (up to 241 kWh), it delivers scalable and dependable power. A 7-inch full-color display, along with Bluetooth, Wi-Fi, and PC connectivity, enables convenient real-time monitoring. Designed to work seamlessly with mainstream inverters via RS485 and CAN communication, the battery also includes built-in wheels and handles for easy installation and mobility
  • Keep Home Running 10kW:ECO-WORTHY 10kW AIO solar charge inverter features 48V DC pure sine wave output with 120V or 120V/240V split-phase support, delivering 10,000W continuous power and up to 20,000W peak output. Equipped with dual MPPT controllers, up to 200A battery charging, built-in WiFi monitoring, multiple charging and output modes, time-slot energy management, and comprehensive protection functions, it is compatible with AGM, Gel, Flooded, and lithium batteries, supports battery-free operation, and allows parallel connection of up to six units
  • High Power Solar Panel:590W Mono-crystalline Solar Panel (Black). Low power loss in cell connection compared to conventional modules. Improved shading tolerance. Lower internal current, lower hot spot temperature. Heat-strengthened glass minimizes micro-crack impact.
  • Shipping Notice: Due to its large size and weight, the 5pcs 590W solar panel/1pc 48V 314Ah battery is securely packed and shipped on a pallet using a truck to ensure safe transportation. Please ensure your delivery address can accommodate truck deliveries.

Calculate baseline emissions

For each billing period or interval group, multiply electricity by the selected baseline factor:

Special offer. See more information about Outbyte and uninstall instructions. Please review EULA and Privacy policy.

Baseline emissions (tCO2e) = baseline electricity (kWh) × baseline factor (kgCO2e/kWh) ÷ 1,000

The division by 1,000 converts kilograms to metric tonnes. If the factor is expressed in grams, convert grams to kilograms first. If the source reports CO2 rather than CO2e, preserve that distinction in the label; do not silently change the gas basis.

For a monthly model, calculate each month separately and sum the results. This prevents a seasonal factor or production pattern from being hidden inside one annual average. For an interval model, apply the factor at the finest resolution supported by the factor source, then aggregate.

Calculate emissions after the switch

Separate electricity still imported from the grid, renewable electricity generated onsite, electricity exported and any storage losses. The core equation is:

Free tools Windows power users keep installed

One-click scans. No signup required.

Special offer. See more information about Outbyte and uninstall instructions. Please review EULA and Privacy policy.

Renewable-case emissions (tCO2e) = grid residual electricity (kWh) × residual or supplier factor (kgCO2e/kWh) ÷ 1,000 + renewable-instrument or lifecycle emissions required by the chosen accounting standard

Onsite generation

Use generation measured at the generator boundary and identify how much serves the factory, how much is curtailed and how much is exported. If batteries are used, account for charging electricity, discharge electricity and round-trip losses according to the selected standard. Do not count the same renewable kWh both as onsite consumption and as exported or certificate-bearing electricity.

PPA or green supply contract

Apply the contract’s delivery and attribute rules to the electricity volume covered. Electricity outside the contract remains subject to the applicable grid or residual factor. Keep contract premiums, settlement charges and certificate costs in the financial ledger even when the market-based emissions factor is zero or lower than the location-based factor.

Calculate avoided emissions and describe the claim

Once both cases use compatible boundaries and factors, calculate:

Special offer. See more information about Outbyte and uninstall instructions. Please review EULA and Privacy policy.

Emissions savings (tCO2e) = baseline emissions − renewable-case emissions

Label the result as location-based, market-based, project-displacement or lifecycle. A market-based renewable-energy certificate claim is not proof that a fossil generator physically reduced output in the same hour. EPA guidance notes that renewable-energy and efficiency impacts require estimating the fossil generation and emissions displaced, and that marginal plants are generally affected rather than always-on baseload. Use “reported contractual reduction” or similar wording when that is what the method supports; reserve “physical hourly reduction” for evidence that demonstrates it.

Calculate electricity-cost savings

Compare the complete cost of the baseline and renewable cases:

Cost savings = baseline total electricity cost − renewable-case total electricity cost

Special offer. See more information about Outbyte and uninstall instructions. Please review EULA and Privacy policy.

For each case, calculate metered kWh multiplied by the applicable energy rate, then add every other charge. Keep avoided costs and new costs as separate rows.

Rank #3
STAR 990W Bifacial Solar Panel, 2PCS 495W UL61730 N-Type Solar Panels
  • Frame-Less Design: Star Cleanedge Series Solar Panel Feature a Frameless Design that prevents dust/water buildup. Rain Self-Cleaning, 0 Maintenance Costs
  • Quality Guarantee: 495W 24 Volt Solar Panels Use 25.6% High-efficiency Cells, Certified by UL, ISO9001, CE, and US Patents, Stable Power Generation Even in Harsh Weather
  • Power Boost: No Frame & Dust Obstruction,15% Increase in Power Generation Compared to Normal Solar Panels
  • Reduce Costs: No Dust Accumulation,Only Rain Cleaning,Saves $3600/year on Cleaning Costs for the Family Travel Fund
  • More Safety: No Need to Clean Rooftops,Climbing-Free,Faster Snow Removal in Winter, Safer to Use
Cost component Baseline case Renewable case Why it matters
Energy charge Imported kWh × tariff rate. Grid kWh × tariff, plus any PPA or supplier energy price. Different rates may apply by time of use or contract settlement.
Demand charge Billable peak kW under the utility rules. Peak after generation, storage and export constraints. Solar may reduce energy kWh without reducing the monthly peak.
Time-of-use effects Load in each price period. Residual load after renewable generation and storage. Generation at a low-price hour may have limited bill value.
Fixed and connection charges Existing service and metering charges. New interconnection, standby or service charges plus existing charges. A lower energy rate can be offset by a new connection fee.
Taxes and balancing Taxes, regulated fees and balancing charges on the existing supply. Taxes, settlement, balancing and certificate or contract charges. PPA invoices may use different tax and settlement lines.
Storage and maintenance Usually none for the baseline unless storage already exists. Charging losses, battery maintenance, inverter maintenance and other operating costs. These are real costs even when onsite generation is free at the point of use.

Use the same currency and tax treatment in both cases. State whether savings are gross or net of taxes, and whether one-time interconnection costs are included in the first-year result or amortized separately.

Estimate payback for onsite projects and PPAs

Simple onsite payback

For an onsite project with an upfront investment, the basic screen is:

Simple payback (years) = net upfront project cost ÷ first-year net electricity-cost savings

Special offer. See more information about Outbyte and uninstall instructions. Please review EULA and Privacy policy.

Net upfront cost should identify equipment, engineering, installation, interconnection, permitting, commissioning and eligible incentives. First-year net savings should use the cost model above and subtract maintenance, insurance, storage losses and any additional fixed charges. A payback number is not a forecast of lifetime profitability: it ignores financing, degradation, replacement, tariff escalation, residual value and savings after the payback date.

PPA payback and contract value

A PPA generally replaces some variable electricity purchases with a contracted price rather than requiring the factory to pay all generation costs upfront. Calculate the annual cash effect as avoided utility energy and demand costs minus PPA energy payments, premiums, settlement, balancing, certificate, connection and residual-grid costs. Include contract escalators, minimum-take provisions, termination charges and the PPA term. If the contract has no upfront investment, report the annual net saving and cumulative cash flow rather than forcing it into an equipment-payback formula.

Use cash-flow years, not one representative month

Build a year-by-year model when tariffs, production, contract prices or renewable output change. Show nominal and, if useful for the decision, discounted cash flows. Keep the emissions model linked to the same generation and load assumptions, but do not convert tonnes of CO2e into money unless the factory has a documented carbon-price or compliance rule.

Independent reader supportYour contribution helps us test, update, and keep practical guides available for everyone.Support on Ko-Fi

Illustrative calculation

The following numbers are purely illustrative arithmetic, not a performance benchmark for any factory. Suppose a site used 12,000,000 kWh in its baseline year and the selected baseline factor was 0.42 kgCO2e/kWh:

What’s actually slowing this PC down?

Pick the symptom - the matching free tool is one click away.

Special offer. See more information about Outbyte and uninstall instructions. Please review EULA and Privacy policy.

12,000,000 × 0.42 ÷ 1,000 = 5,040 tCO2e baseline emissions

After the switch, suppose 5,000,000 kWh remains grid-imported and the applicable residual factor is 0.38 kgCO2e/kWh. Suppose the chosen accounting rule assigns 20 tCO2e of lifecycle emissions to the renewable supply:

5,000,000 × 0.38 ÷ 1,000 + 20 = 1,920 tCO2e renewable-case emissions

The resulting reported saving is:

5,040 − 1,920 = 3,120 tCO2e

For costs, assume the baseline’s complete annual bill is $1,800,000 and the renewable case totals $1,420,000 after energy, demand, fixed, balancing, connection, storage and maintenance lines are included. The annual saving is $380,000. If the net upfront project cost were $1,900,000, the simple payback screen would be 5 years, subject to the limitations of that metric.

Special offer. See more information about Outbyte and uninstall instructions. Please review EULA and Privacy policy.

Run low, base and high cases

Do not report a single precise number when key inputs are uncertain. Create at least three cases and show which assumption changes in each one.

  • Grid factor: use the credible low and high factors for the selected geography, year and accounting basis.
  • Renewable generation: vary expected output, degradation, availability and commissioning date.
  • Curtailment and exports: test how much generation cannot be consumed onsite or credited under the contract.
  • Load growth: model planned production increases, new equipment and efficiency projects.
  • Tariff escalation: vary energy and demand-rate changes separately.
  • Demand peaks: test whether renewable generation or storage actually coincides with the utility’s demand-measurement window.
  • Contract price: vary PPA escalators, settlement prices, certificate costs and balancing charges.

Report the range, the base case and the variables that drive the spread. A narrow range created by changing only the grid factor is misleading if demand charges or renewable output are more influential financially.

Build an audit trail a reviewer can reproduce

Store the following with the calculation:

  • Original interval-meter exports and submeter files.
  • Utility bills, tariff sheets and demand-charge rules.
  • Renewable-generation, inverter, curtailment and export records.
  • PPA, supplier, interconnection, storage and maintenance contracts.
  • Energy-attribute certificates and delivery or matching evidence.
  • The exact emissions-factor workbook, factor name, geography, unit, publication year and download date.
  • Boundary, counterfactual, production-normalization and lifecycle assumptions.
  • Formula versions, data-cleaning logs, scenario inputs and reviewer sign-off.

Use version control for factor files and formulas. If a factor is updated after the reporting year, preserve the factor originally used and document any restatement rather than overwriting the evidence.

Rank #4
SUNGOLDPOWER 16BB N-Type 4pcs 560W Bifacial PERC Solar Panels Monocrystalline,High Efficiency up to 30%, High Power PV Module for Off-Grid, Residential & Commercial Solar Systems(4pcs 560W Bifacial)
  • 【High Efficiency】 : SUNGOLDPOWER 16BB N-Type 560W Bifacial monocrystalline PERC solar panel can generate more energy up to 30%
  • 【High Tolerance】: SUNGOLDPOWER 560W Bifacial Solar panels offer higher durability even rough climatic heat /cold/snow/wind.
  • 【Widely Use】: SUNGOLDPOWER 560 watt Bifacial solar panels can be set up at any angle. No need to analyse or calculate the right mounting and tilt angle. Embrace a variety of installation methods and strategically plan your energy solution!
  • 【Up to 30% Residential Clean Energy Credit】 You might be eligible for this tax credit if you own a solar PV system that was installed in the US between January 1, 2017, and December 31, 2034.

Common failure modes and fixes

Using a generic internet grid factor

Failure: Applying one worldwide number to a factory without stating geography or year.

Free tools Windows power users keep installed

One-click scans. No signup required.

Special offer. See more information about Outbyte and uninstall instructions. Please review EULA and Privacy policy.

Fix: Select the factor for the connected region and reporting year, record its source and distinguish location-based from contractual or displacement accounting.

Using apparent power or an unverified meter multiplier

Failure: Calculating from kVA, reactive power or a CT ratio that was never checked.

Fix: Use active real-power kWh, verify the multiplier and reconcile totals to bills.

Ignoring demand charges

Failure: Multiplying all kWh by an energy rate and calling the difference bill savings.

Special offer. See more information about Outbyte and uninstall instructions. Please review EULA and Privacy policy.

Fix: Model demand peaks, time-of-use windows, fixed charges, taxes, balancing, connection and storage lines separately.

Counting certificates as physical hourly displacement

Failure: Treating a market-based instrument as proof that the local grid emitted less in the same hour.

Fix: State the contractual claim and use a project-displacement method only when its counterfactual and dispatch evidence are available.

Double counting renewable electricity

Failure: Counting one kWh as onsite consumption, an export and a certificate-backed delivery.

Special offer. See more information about Outbyte and uninstall instructions. Please review EULA and Privacy policy.

Fix: Track generation, self-consumption, storage charging, discharge, curtailment, exports and attributes as separate quantities.

Presenting a forecast as a measured saving

Failure: Reporting modeled generation or avoided emissions without identifying assumptions.

Fix: Label forecasts, measured results and counterfactual estimates separately, and publish the low/base/high range.

A practical implementation checklist

  1. Name the site, meters, production boundary and connected grid system.
  2. Choose the comparison months and document production and operating conditions.
  3. Export interval active-energy data and reconcile them to every bill.
  4. Separate imported, onsite-generated, stored, exported and curtailed electricity.
  5. Choose and document the emissions-factor basis, geography, year, unit and source.
  6. Write the no-project counterfactual and any confidence adjustment.
  7. Calculate baseline and renewable-case emissions with visible formulas.
  8. Build a full bill model with energy, demand, time-of-use, fixed, tax, balancing, contract, connection, storage and maintenance rows.
  9. Run low, base and high cases for factor, output, curtailment, load, tariffs, peaks and contract price.
  10. Have an independent reviewer check the data lineage, formulas, claims and sign-off package.

The strongest result is not the largest number of tonnes or dollars. It is a result whose boundary, meter data, factor, counterfactual, cost rows and uncertainty can all be traced back to evidence.

What’s actually slowing this PC down?

Pick the symptom - the matching free tool is one click away.

Special offer. See more information about Outbyte and uninstall instructions. Please review EULA and Privacy policy.

Product prices and availability are accurate as of the date/time indicated and are subject to change. Any price and availability information displayed on Amazon at the time of purchase will apply.

Electricity Costsemissions factorsfactory operationsonsite solarPPArenewable energyScope 2 emissions

Leave a Reply

Your email address will not be published. Required fields are marked *

Special offer. See more information about Outbyte and uninstall instructions. Please review EULA and Privacy policy.

Recommended PC Tool
Recommended PC Tool
Windows Errors? Fix Them Before They SpreadFree repair scan
Outdated Drivers Are Slowing You DownFree scan - exact matches

Two free Windows tools

One Free Minute Could Fix That PC

Before you go - each of these free tools takes about a minute and tackles what quietly slows a Windows PC down.

Special offer. View Outbyte info, uninstall instructions, EULA, and Privacy Policy.