Halloween DealsAmazon USHalloween week deals: useful picks before month-endAmazon US: current deals, useful picks and tech finds.Check DealsSlow PC?RecommendedPC slow today? Run a repair scan before it gets worseResolve common Windows issues and optimize system performance.Scan NowHalloween DealsAmazon USOctober picks are moving - compare before checkoutAmazon US: current deals, useful picks and tech finds.See Picks×
Skip to content
World desk4 min

What Data Centers Use Electricity and Water For—and How to Compare Their Impact

Data centers power servers, storage and networking, then spend more electricity on facility support such as cooling and power distribution. Water comparisons depend on whether they count on-site cooling or electricity generation.
Special offer. See more information about Outbyte and uninstall instructions. Please review EULA and Privacy policy.

Data centers use electricity to run servers, storage and networking equipment, and to keep that equipment powered and cool. Water use is chiefly tied to cooling at sites that use evaporation; there can also be an indirect water footprint from generating the electricity a facility consumes. To compare impacts fairly, separate those accounting boundaries, name the location and year, and look at total use as well as efficiency ratios.

What do data centers use electricity and water for?

A data center’s electricity use has two broad parts: the energy used by information technology (IT) equipment and the energy used by facility infrastructure that supports it. The IT load includes servers doing computation, storage systems, and networking equipment moving data. Facility overhead includes cooling and losses in power distribution.

As an Amazon Associate I earn from qualifying purchases.

The split varies with the site and how its equipment is operated. In a modeled U.S. estimate, the Department of Energy and Lawrence Berkeley National Laboratory (DOE/LBNL) put facility infrastructure at 31% of data-center electricity in 2024, down from 36% in 2018. Networking accounted for 4.5% in 2024. These are U.S. estimates, not a universal breakdown for every data center. DOE/LBNL, United States Data Center Energy Usage Report: 2025 Update

Special offer. See more information about Outbyte and uninstall instructions. Please review EULA and Privacy policy.

Cooling uses electricity and, in some systems, water

Cooling removes heat produced by IT equipment. Some cooling designs use evaporative heat rejection: water evaporates to carry heat away, so the system needs makeup water. Cooling towers may also discharge blowdown to control the concentration of dissolved minerals. The balance of water and electricity use depends on cooling design, local climate and operating conditions. DOE Federal Energy Management Program, Cooling Water Efficiency Opportunities for Federal Data Centers

#1 Best Overall
AC Infinity AIRPLATE S1, Quiet Cabinet Cooling Fan 4" w/ Speed Controller
  • An ultra quiet fan system designed for cooling cabinets that requires minimal noise.
  • Features a multi speed controller to set the fans speed to optimal noise and airflow levels.
  • Contains a CNC machined aluminum frame with a modern brushed black finish.
  • Powered by wall outlet or USB port, included Turbo Adapter increases performance by 25 percent.
  • Dimensions: 4.6 x 4.6 x 1.3 in. | Airflow: 26 CFM | Noise: 17 dBA | Bearings: Dual Ball

Cooling’s share of electricity is not fixed. The International Energy Agency (IEA) reports that it can range from about 7% in efficient hyperscale data centers to more than 30% in less-efficient enterprise data centers. That comparison describes a range across types of facilities, not a prediction for an individual site. IEA, Energy and AI: Energy demand from AI

Water has direct and indirect boundaries

On-site water use is often associated with cooling, particularly where evaporative systems are used. A second boundary counts water consumed in generating the electricity supplied to a data center. LBNL distinguishes these as direct or site water and indirect or source water. They are different quantities: a total that counts only water at the facility cannot be compared directly with one that also includes water used in electricity generation. LBNL, 2024 United States Data Center Energy Usage Report

Rank #2
VTRETU Router Cooling Fan for Computer Cooler Audio Video Network Cabinet Server Cooling Project Equipment and Workstation DC 5V USB Power 120mm 360mm Fan with Switch
  • 【better after-use experience】 Temperature reduction provides an expected longevity extension and higher performance of a critical network component,These fans are overall very helpful for devices that get a bit hot and start to throttle down.
  • 【choice of most users】It works great ,for DIY cooling fan or as an additional cooling ,fan for your gaming needs. like as router, cabinet, Modem, DVR, Receiver, Streaming ,boxes, x-box, SSD, Security Camera NVR, andriod box, stereo, T-Mobile gateway. Good balance of quiet and airflow. keeping electronics cool .Three specifications of fans, suitable for more usage scenarios .
  • 【Custom shock absorbing feet】 four feet using environmentally friendly rubber, after testing, the softness of the feet that can smoothly grab the desktop, not too hard and desktop resonance .
  • 【Fan parameters】Connecter: USB; Cable Length: 55cm Or 21 inches; Bearing type: Sleeve ; Life: 35000 hours / Dimension: 360mm(L) x 120mm(W) x 25mm(H) / 4.7x4.7x1 in. per fan; Rated Voltage:5V 0.2A; Speed: 1500RPM; Air flow: 56.7CFM; Noise:23dBA .
  • 【Warranty & Packing List】Warranty: One-year quality assurance. Please contact us, If the product has any quality problems, it will be refunded within 90 days or replaced within one year | Packing list: A finished product .

Electricity-related water use varies with the power supply, while on-site water consequences depend on the cooling system and local conditions. A national or global average therefore cannot establish the water impact of a particular data center. The available official figures cited here do not establish a single current global water total suitable for an unqualified comparison.

Special offer. See more information about Outbyte and uninstall instructions. Please review EULA and Privacy policy.

How much electricity do data centers use?

For scale, the IEA estimates that data centers worldwide used 415 terawatt-hours (TWh) of electricity in 2024, about 1.5% of global electricity use. This is a global estimate for a specific year. IEA, Energy and AI: Energy demand from AI

Rank #3
Jingchengmei 2U Cantilever Server Rack Shelf 2 Piece Set Center Weighted
  • Compatible with all 19” racks and cabinets to hold various IT, network and other equipment.
  • Dimensions: W 19" x D 10" x H 2U per shelf ; 2 Shelves as set
  • This Vented Center Weighted Mounting Rack Shelf fits the mounting posts in different deepth from 75 mm to 125mm.
  • Max Weight Capacity: 110 Pounds; Center weighted.
  • Slotted Venting to Improve Air flow and Help Prevent Overheating of Your Equipment

For the United States, the 2025 DOE/LBNL update gives a modeled central estimate that data centers could consume 11.8% of U.S. electricity by 2030. Its scenario range is 9.5% to 15.3%. These are projections, not measured 2030 outcomes. DOE, Powering America’s AI Future—Data Center Resource Hub

An earlier DOE/LBNL report estimated U.S. data centers used 176 TWh, or about 4.4% of U.S. electricity, in 2023. That 2024 report projected 325–580 TWh by 2028; the projection is historical and has been superseded for current U.S. forecasting by the 2025 update. DOE, DOE Releases New Report Evaluating Increase in Electricity Demand from Data Centers, December 20, 2024

Rank #4
QYXJAEO 9U Wall Mount Server Rack Cabinet for 19'' IT Equipment, AV Device
  • Space-Saving Design: Measures 19.0"H x 21.7"W x 17.7"D with a 14.2" max mounting depth, our 9U rack fits tight spaces while holding full 19" gear—ideal as a server cabinet or wall mount network cabinet for home offices and small server rooms
  • Full Security: Both the lockable glass door and side panels protect your hardware from theft or tampering. This 9U wall mount rack gives you peace of mind in public or shared environments, ensuring your equipment rack stays safe and secure
  • Active Cooling: The built-in cooling fan prevents overheating, keeping your wall mount server rack running reliably. Perfect for active networks, this 9U network rack extends the life of switches, routers, and PDUs by maintaining consistent airflow
  • Heavy-Duty Build: Cold-rolled steel construction supports up to 110 lbs of 19" IT and A/V devices. Whether you need a wall mount server cabinet for shallow servers or a wall mount network rack for patch panels, this delivers years of reliable use
  • Easy Installation: Pre-marked mounting holes and top/bottom cable ports make setup fast. Adjustable rails and numbered U positions allow precise rack mounting of your gear. This turns any wall into a tidy, professional server room in minutes

The global 2024 estimate and U.S. forecasts cover different geographies and periods. They should not be read as directly comparable values or treated as parts of a single trend without aligning their boundaries and dates.

Special offer. See more information about Outbyte and uninstall instructions. Please review EULA and Privacy policy.
Independent reader supportYour contribution helps us test, update, and keep practical guides available for everyone.Support on Ko-Fi

How can you compare their impact?

Start by asking what the figure counts. A data-center claim may describe IT equipment alone, the full facility, on-site water, or water associated with electricity generation. Before comparing two figures, check that they use compatible boundaries, geography and reporting years.

Best Value
MovinCool Climate Pro K63 Commercial Portable AC Unit
  • Color LCD control panel. Simplifies operation, clearing of codes and easier to read.
  • Matte black cabinet brings stylish utility to the workplace.
  • Added bumpers enable safer handling and movement around your facility.
  • Larger casters makes rolling and navigation easier.
  • Cools to mid-60s °F — for effective heat control around electronics, servers, and computers.

Read efficiency ratios alongside total use

  • PUE (Power Usage Effectiveness) compares total facility energy with energy used by IT equipment. It indicates how much energy the facility uses beyond the IT load; it does not state the facility’s total electricity consumption on its own.
  • WUE (Water Usage Effectiveness) compares water consumption with IT electricity and is commonly reported in liters per kilowatt-hour. Check whether a WUE figure counts direct/site water, indirect/source water, or another stated boundary.

PUE and WUE are efficiency indicators, not substitutes for absolute electricity and water totals. A ratio alone also cannot show whether water use puts pressure on a particular local supply. For a useful comparison, pair each ratio with the amount consumed and the period measured.

Check cooling, climate and electricity supply

Cooling arrangements—including evaporative cooling, air-side economizing and direct liquid cooling—affect the facility’s electricity and water balance. Outdoor conditions affect how systems operate. The electricity supply matters too, because the water consumed to generate electricity varies by location and generation mix. A meaningful site-level comparison therefore needs more than a national average or an efficiency score.

Separate observed estimates from forecasts

Record who produced a number, what year it covers, whether it is an estimate or a scenario forecast, and whether it describes one country or the world. For instance, the IEA’s 415 TWh figure is a global 2024 estimate, while DOE/LBNL’s 11.8% figure is a modeled U.S. scenario for 2030. Keeping those labels attached prevents unlike numbers from being mistaken for competing measurements.

Special offer. See more information about Outbyte and uninstall instructions. Please review EULA and Privacy policy.

Quick Recap

Bestseller No. 1
AC Infinity AIRPLATE S1, Quiet Cabinet Cooling Fan 4' w/ Speed Controller
AC Infinity AIRPLATE S1, Quiet Cabinet Cooling Fan 4" w/ Speed Controller
An ultra quiet fan system designed for cooling cabinets that requires minimal noise.; Contains a CNC machined aluminum frame with a modern brushed black finish.
$25.99
Bestseller No. 3
Jingchengmei 2U Cantilever Server Rack Shelf 2 Piece Set Center Weighted
Jingchengmei 2U Cantilever Server Rack Shelf 2 Piece Set Center Weighted
Dimensions: W 19" x D 10" x H 2U per shelf ; 2 Shelves as set; Max Weight Capacity: 110 Pounds; Center weighted.
$39.99
Bestseller No. 5
MovinCool Climate Pro K63 Commercial Portable AC Unit
MovinCool Climate Pro K63 Commercial Portable AC Unit
Color LCD control panel. Simplifies operation, clearing of codes and easier to read.; Matte black cabinet brings stylish utility to the workplace.
$12,999.00

Product prices and availability are accurate as of the date/time indicated and are subject to change. Any price and availability information displayed on Amazon at the time of purchase will apply.

Leave a Reply

Your email address will not be published. Required fields are marked *

Special offer. See more information about Outbyte and uninstall instructions. Please review EULA and Privacy policy.

More from the Wire

  1. World desk4 min
    How to Spot an AI Voice Scam Before Sending MoneyDon’t rely on how a caller sounds. Pause, call back through a known number, and verify the emergency with another trusted person before sending money.
  2. Mountain View desk4 min
    Google’s SynthID Detector: How to Check AI-Generated Images, Video and AudioGoogle’s SynthID Detector looks for an embedded watermark in supported images, video and audio. Here is what its results do—and do not—show.
  3. Redmond desk20 min
    How to create a link to File or Folder in Windows 11Windows 11 gives you several ways to point to a file or folder without moving or duplicating it. You can create a desktop shortcut,…
Recommended PC Tool
Recommended PC Tool
Crashes, No Sound, or Screen Glitches?Free driver scan
PC Slower Than It Used to Be?Free scan - under a minute

Two free Windows tools

One Free Minute Could Fix That PC

Before you go - each of these free tools takes about a minute and tackles what quietly slows a Windows PC down.

Special offer. View Outbyte info, uninstall instructions, EULA, and Privacy Policy.