Italy has received connection applications for nearly 600 data-centre projects totaling more than 100 gigawatts (GW), Terna CEO Pasqualino Monti said on 14 October 2026. The figure describes requested grid capacity—not 100 GW of data centres under construction—and Terna says many applications exceed the country’s practical ability to build them.
What Terna announced
Speaking at the RCS Academy Green & Net Zero Talk, Terna CEO Pasqualino Monti said the transmission operator had received requests linked to almost 600 data-centre initiatives with a combined capacity above 100 GW. Reuters reported the statement and noted that the requested total was 42 GW in May 2025.
As an Amazon Associate I earn from qualifying purchases.
Monti’s qualification is central to interpreting the headline. He said the connection requests “far exceed the real capacity to implement the projects” and described the challenge as supporting the sector’s growth “efficiently and gradually.” In other words, developers have asked Terna to reserve or study grid connections; those applications still have to mature through planning, financing, permits, construction and energisation.
The Tool Desk
Outbyte Driver Updater FREEFix the driver behind crashes, sound loss and screen glitchesFind Drivers →Outbyte PC Repair FREEClear out junk files and repair common Windows errorsFree Scan →Monti also called data centres strategic to Italy’s digital and energy transformation. He linked demand to cloud computing, artificial intelligence, 5G and other digital services, and said Terna’s scenarios already include rising data-centre electricity consumption.
#1 Best Overall
- 8 POWERFUL NEMA C13 OUTLETS: Rack mount PDU provides up to 16A/120V (1920VA) or 20A/240V (4800 VA) for servers & equipment; 1U rack space for easy accessibility; 10ft/3m C19 to NEMA5-20p cord incl.
- 3600 JOULE CIRCUT PROTECTION: Built-in resettable circuit breaker that acts as a surge protector or shields from unintentional overloads in data center; Safety listed for performance and peace of mind
- CONFIGURABLE EIA-310D COMPLIANT DESIGN: Installable in standard 19in. 2 or 4 post rack using incl. cage nuts/screws; C20 power cord allows any local plug config for 120 or 240 V single phase in/out
- SPECS: 1U 19in. Horizontal PDU | 8x IEC C13 Pwr out | C20 Pwr input (1 phase) | Load cap. @ 120V/16A (1920VA) |Load cap. @240V/20A (4800VA) | 3600 J surge sup. w/breaker |EIA-310D |Mounting H.W. incl.
How the request pipeline grew
Terna’s published milestones show a rapidly expanding queue of applications. Each figure below is a request or application total, not commissioned data-centre capacity.
| Date | Reported request total | What it represents |
|---|---|---|
| End of 2024 | About 30 GW | Data-centre connection requests in Terna’s earlier pipeline |
| 28 February 2025 | 39.62 GW | Figure in Terna’s 2025 Development Plan |
| May 2025 | 42 GW | Total reported by Reuters from Terna information |
| 30 June 2025 | Over 50 GW across more than 300 projects | Terna Lightbox explainer |
| End of January 2026 | Almost 80 GW | Figure in Terna’s 2025 Annual Report |
| 14 October 2026 | More than 100 GW across nearly 600 initiatives | Statement by Terna CEO Pasqualino Monti |
The sequence indicates that proposed demand more than tripled from roughly 30 GW at the end of 2024 to above 100 GW in October 2026. It does not indicate that Italy’s operating data-centre load tripled over the same period; it indicates that the queue of proposed connections grew.
Rank #2
- Versatile and Space-Saving: This 1U Rack mount PDU features a compact design that allows for efficient use of space in standard 19-inch racks. 16 rear-facing plug outlets and three front-facing outlets provide ample connectivity for your devices
- Efficient USB Power: Featuring four USB ports, it enables simultaneous power supply to your favorite devices, ensuring convenience and productivity
- Built-in Circuit Breaker: The PDU is equipped with a built-in 12-Amp circuit breaker that protects against circuit overloads. This ensures reliable performance and helps prevent damage to your equipment
- Heavy-Duty Construction: The power distribution unit is designed with heavy-duty components and a sturdy metal housing for durability and long-lasting use
- Convenient Mounting: The PDU features mounting ears on the back panel for easy installation in a standard 19-inch rack
How many data centres are actually operating?
The application count should not be confused with Italy’s existing estate. Data from the Data Center Observatory at Politecnico University, cited by Reuters, puts the number of operating data centres at about 205. The same source says the Milan area accounts for 68% of Italy’s data-centre power capacity. Reuters also cited 83 projects expected through 2028, with potential investment of up to €25 billion. Those projects are a subset of the much larger connection-request queue and should not be treated as a guarantee that all will be built.
Where are the proposed facilities concentrated?
Northern Italy and Lombardy
Terna’s 2025 Development Plan says requests are concentrated mainly in northern Italy. Milan and surrounding Lombardy are the most important cluster: the observatory’s 68% figure refers to the area’s share of existing Italian data-centre power capacity, not 68% of every future application. The concentration reflects established digital-services demand, network connectivity, industrial land and access to major electricity infrastructure.
Rank #3
- Reliable Power Distribution - Backed by a 3 year warranty, this power strip surge protector can deliver 120, 125, or 240V AC at 15 or 30A, optimized for networking, telecom, crypto mining, or security.
- Designed For Your Safety - This rack mount PDU has a built-in surge protector to help minimize overloads. It also has volt and amp meters in it with a clear display for convenient monitoring of loads.
- Power Up Your Server - This PDU power strip can fit in 1U of EIA-standard 19” server racks with two or four posts. It’s switchless to avoid accidental shutdowns that can lead to costly downtimes.
- Connect Multiple Loads - Our rack mount power strips have 6 or 8 C13 rear outlets, a NEMA L6-30P input plug, and a 6’ or 10’ heavy-duty cable for connecting to a utility outlet, generator, or UPS.
- Easy Installation - This power strip has a reversible 19" metal case so it can face either the front or rear of your rack. Ears and fittings are included in the rack mount for faster PDU installation.
Why location matters to the grid
A large load in one region cannot necessarily be balanced by generation elsewhere without adequate transmission and transformation capacity. Clusters therefore affect which substations, high-voltage lines and local planning processes need reinforcement. A project’s distance from available capacity can be as important as its headline power requirement.
Why 100 GW of requests is difficult to connect
Individual sites are very large loads
Terna says a hyperscale data centre commonly requires 100–200 megawatts (MW) of power. Some applications exceed 500 MW. These are continuous, high-quality loads rather than occasional peaks, so a connection study must examine firm capacity, fault levels, voltage stability, redundancy and the ability to serve the site during network outages.
Rank #4
- 100-125V/15A Basic Power Distribution Unit (PDU) delivers AC power to data centers, network closets, and other electrically demanding applications
- OUTPUT: 10 Rear NEMA 5-15R Outlets; INPUT: NEMA 5-15P straight plug with 15 ft power cord
- VERSATILE RACKMOUNT OPTIONS: Allows for the PDU to be installed vertically or horizontally
- ADDITIONAL FEATURES: Network-grade plugs and outlets, durable metal housing, and cord retention tray
- 3-YEAR LIMITED WARRANTY (This unit does not provide surge suppression)
Infrastructure and approvals take time
Connecting the pipeline can require new transmission infrastructure or upgrades to existing lines and substations. Developers also need land, construction permits, environmental approvals, equipment and financing. Terna’s planning documents describe a managed connection process, which means an application can be revised, delayed, rejected or withdrawn before any electricity flows.
Do these 3 things before closing this tab:
1Clear out junk files and repair common Windows errors2Scan for outdated or missing drivers - takes under a minute3Repair Windows errors before they cause bigger problemsThe queue contains projects at different stages
Nearly 600 initiatives are not equivalent: some may be early-stage concepts, while others may have advanced technical studies or secured sites. The aggregate number is useful for stress-testing long-term scenarios, but it cannot predict the final number of facilities or their combined operating load.
Best Value
- 【Heavy-Duty 9 Outlet PDU】 Designed for standard 19" server racks, this 1U rack mount power strip provides 9 US standard outlets (15A/125V/1875W), ideal for data centers, network cabinets, and audio-visual setups needing reliable power distribution.
- 【Individual Switch Control】 Each outlet is equipped with its own illuminated on/off switch, so you can manage connected devices individually instead of unplugging them. The switch modules are fully independent: if one outlet trips, only that outlet shuts down while all remaining outlets keep running normally — no whole-strip shutdown, no interruption to your other equipment. A tripped switch also tells you exactly which device has reached its load limit, giving you faster, more sensitive overload protection and a clear visual cue for troubleshooting.
- 【Overload Protection & Power Monitoring】 Equipped with overload protection and a digital power monitoring display, this PDU safeguards your equipment from overloads while providing real-time voltage and current data for secure operation. The switch will automatically trip if the current exceeds 15A. Simply having wires or cables touch the switch will not cause it to trip — the switch only responds to an overload condition.
- 【Durable Metal Construction】 Built with a sturdy metal housing and a 14AWG heavy-duty 6.5FT power cord, ensuring durability and stable performance even in high-demand environments like professional server rooms and industrial settings.
- 【Versatile Installation】 Ideal for studios, labs, and data centers, ensuring peak performance and reliability. Designed for 1U rackmount for hassle-free cable management. Supports horizontal installation in server racks with included mounting brackets.
Can Italy’s grid handle the demand?
There is no evidence that the entire 100-plus-GW queue can be connected immediately. Monti explicitly said the requests exceed the real capacity to implement the projects. Terna’s response is therefore staged: assess which projects are credible, coordinate connection timing, and invest in the transmission and substation upgrades needed for projects that mature.
That approach does not mean Italy will reject data centres. It means energisation will depend on regional grid capacity, permitting schedules and project readiness rather than on the order in which applications arrived. Terna says its scenarios already account for higher data-centre consumption, giving planners a basis for deciding where reinforcement is justified and how quickly it can be delivered.
What to watch next
- Whether applicants progress from connection requests to accepted technical solutions and binding agreements.
- Which northern Italian substations and transmission corridors receive investment approvals.
- How many of the announced projects secure permits, financing and land.
- Whether demand is distributed beyond the Milan and Lombardy cluster or remains heavily concentrated there.
- Terna’s future updates on realised connections and actual electricity consumption, which will be more meaningful than the application total alone.
Italy’s 100-GW headline is therefore best read as a measure of developer interest and a planning challenge. It signals potentially major growth in digital infrastructure, while the number of facilities ultimately built will be much smaller than the raw queue unless projects pass the technical, commercial and regulatory tests required for connection.